Hydro_Gen > The one thing stumping me right now is the installation calls for 14 AWG X 3 from the compressor to the indoor air handler (all on a 20 amp circuit) yet there are only 2 terminals
Micro > R U sure the instructions on the 14/3 wire do not refer to Power wire (red or black), a return wire (usually white), and a ground wire ???
Zim : My guess would be the two terminals are for 220 VAC. No need for a neutral.
But do check the manual for the unit, and or call the manufacturer to make certain.
Zim.